| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-00-063-8997 Item Description: CIRCUIT BREAKER | 5925 | 000638997 | 0 | P | ||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| U | A | 0 | ||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| ETN277300S22 | 2 | 2 | 3 |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | ||
| ABKW | OVERALL HEIGHT | 4.125 INCHES NOMINAL |
| ADTV | CASE MATERIAL | PLASTIC |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| APNQ | ARC QUENCHING METHOD | AIR |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CPLM | UM CONTINUOUS LOAD CURRENT RATING PER POLE | 75.0 AMPERES AC ALL LOCATIONS AND 75.0 AMPERES DC ALL LOCATIONS |
| CPRG | UM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 145.0 ALL LOCATIONS |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +900.0/+1050.0 AC ALL LOCATIONS |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
| FREQ | FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
| ABHP | OVERALL LENGTH | 6.500 INCHES NOMINAL |
| ABMK | OVERALL WIDTH | 4.875 INCHES NOMINAL |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
| CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 20.000 MINIMUM AT 600 PCT ALL LOCATIONS AND 32.000 UM AT 600 PCT ALL LOCATIONS |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT, FEMALE |
Warrantied inventory at competitive prices
Search the world's largest inventory of electronic components by manufacturer, category or part number
All inventory ready to ship from our sellers
We sell only warrantied and traceable parts
Semiconductor's Certifications and Memberships
We are most trusted and leading distributor for aviation parts. You can get a quote within 15 minutes for your desired part. Quote Now!
Request for Quote